The extraction capacities for this models just depends the dosing flow rate and for that recommendable understand the indicated volume as a hourly capacity assuming 60 minutes maturation time that is the standard for most polyelectrolyte manufacturers.
Main structure built in HDPE with classic three chambers parallelepiped geometry connected by overflow channels permitting distinct solution volumes for dilution, maturation and dosing.
The duty cycle is controlled by ultrasonic continues level measuring sensor, installed in the dosing chamber, that start the refilling process automatically, opening the solenoid valve and adjusting the dry feeder speed to get always the selected concentration even with water flow variations.
Configurable process alarms with informative or impeditive action. Mechanical and process fault alarms with independent contact free current signals.